TRADESBRAIN / WORKED CASE / 2026-09-23
3.5-TON ROOFTOP UNIT: RUNNING BUT NOT COOLING, SUCTION 148 PSIG
A tech gets a no-cool call on a 3.5-ton R-410A package unit on a roof. Everything runs: the compressor is on, the condenser fan is on, air comes out of the registers. But the space is 80°F and climbing on a 95°F day. His gauges say low-side 148 psig and high-side 252 psig. The return air at the unit is 78°F and the air at the register is 63°F — a delta-T of about 15°F. No ice anywhere on the coil or the lines. This page works the case the way a careful diagnostic tech would: separate what is known from what is assumed, rank what is probably wrong with the evidence for and against each cause, and pick the one test worth doing next.
STEP 1 — THE EVIDENCE, TYPED
FACT: unit runs, air moves, space not cooling (80°F at the thermostat, 95°F outdoors)
MEASUREMENT: low-side 148 psig, R-410A
MEASUREMENT: high-side 252 psig
MEASUREMENT: return air 78°F at the unit
MEASUREMENT: supply air 63°F at the register, delta-T ~15°F
OBSERVATION: no ice on the coil or lines
MISSING: superheat, subcooling, return-air wet-bulb, amp draw
ASSUMPTION: airflow is correct (filter clean, blower tap untouched)
ASSUMPTION: the charge has not been disturbed since install
On R-410A at 95°F outdoors, suction in the high 140s is well above the ~115–130 psig a healthy 3.5-ton system should show, and 252 psig of head is below where this unit should run on a 95°F day. High suction with soft head means the compressor is not lifting what it should — either because refrigerant is flooding back to it, or because it cannot build pressure in the first place. The two most useful numbers are missing: superheat and subcooling. Every hypothesis below leans on one of those, which is exactly why they are the next measurement.
STEP 2 — PROBABLE CAUSES, RANKED
#1 TXV stuck open or sensing bulb lost contact (refrigerant overfeed)
For: An overfeeding metering device dumps liquid back to the compressor: suction rises toward standing-pressure values, head sags because the compression ratio collapses, the coil floods and delta-T drops to the ~15°F seen here. The most common mechanical reason is a bulb strap that worked loose or a bulb that was never moved off the install position.
Against: No superheat number exists yet — without it this cause is a pattern match, not a confirmation. Low delta-T alone is also consistent with causes #2 and #3.
#2 Compressor inefficiency (worn scroll, failing to build pressure)
For: A tired compressor shows exactly this gauge pair: high suction, low head, warm-ish supply air. Head at 252 psig on a 95°F day is lower than this unit should make even before anything else is wrong.
Against: Scroll units rarely degrade gradually — they usually fail loudly or not at all. And an overfed compressor (cause #1) produces the same low compression ratio, so the gauges alone cannot separate them.
#3 Low evaporator load (wet coil, high indoor humidity, high return temp)
For: A coil carrying a heavy latent load runs high suction and cool-but-not-cold supply air. On a muggy 95°F day the return-air wet-bulb — never measured here — decides how the gauges should be read.
Against: It explains the high suction, but it fights the delta-T: a load-driven high suction normally comes with a LOW delta-T of 8–12°F, not the 15°F measured here. That conflict is why it ranks below the overfeed.
#4 Overcharge from a previous service visit
For: Extra refrigerant raises suction and floods the compressor; the assumption that nobody has touched the charge since install is unverified.
Against: An overcharge pushes head pressure UP, and 252 psig is soft, not high. If the charge were the story, the head would tell it.
#5 The readings themselves are wrong (bad gauge core, thermometer in the wrong spot)
For: Schrader depressors and tired gauge sets skew both numbers, and a register thermometer reads mixed air if it sits near a diffuser vane.
Against: The customer complaint (space not cooling) matches the gauge story independently. Two errors agreeing by accident is less likely than either single cause.
STEP 3 — WHAT IS RULED OUT, AND WHY
Low charge: mostly ruled out — a system this short on refrigerant shows LOW suction and an iced or starved coil, and this unit has neither. Dirty condenser / high head: ruled out by the 252 psig head, which is soft, not high. Frozen evaporator from low airflow: ruled out by the observation, though the assumption behind it — that airflow is healthy — has not been tested, and a slipping blower belt or a collapsed filter is a two-minute check that closes it. What is not ruled out, only assumed away: that no one has added or recovered charge since the unit was set. If a previous company “topped it off,” causes #1 and #4 change places.
STEP 4 — THE ONE TEST WORTH DOING NEXT
> Measure evaporator superheat at the TXV bulb and subcooling at the liquid line, with a clamp-on probe — while confirming the bulb strap is tight and insulated.
What each result would mean: superheat below ~6°F with normal subcooling → the valve is overfeeding, cause #1, and the fix starts with the bulb before any valve is replaced. Superheat normal but subcooling low and amps soft → the compressor is not pumping, cause #2, and it is time for a compression-ratio check, not refrigerant. Both high → charge, cause #4, recover to nameplate and weigh it in.
This test is chosen because it costs ten minutes and two clamp-on probes, splits the top three causes in one shot, and — because the strap check rides along with it — often ends the call before it starts. The expensive wrong move is the one this trade sees too often: gauging in, seeing high suction, and adding refrigerant to a flooded system. On R-410A that overcharge can slack the head further, flood back harder, and take the compressor with it.
QUESTIONS THIS CASE KEEPS GETTING
What should the delta-T be on an R-410A rooftop unit?
Most healthy systems run a supply-to-return split of roughly 16–22°F, and high indoor humidity narrows it — so 15°F on a muggy day is borderline on its own, not a verdict. It becomes a red flag when it travels with suction pressure that is too high, which is the pattern in this case: the coil is being fed more refrigerant than it can boil off, or the compressor is not lifting what it should.
High suction pressure on R-410A — is that a bad compressor?
Not by itself. High suction with soft head pressure means the compression ratio is low, and two different failures produce that: a metering device overfeeding liquid back to the compressor (TXV stuck open, bulb strap loose) or a compressor too worn to build pressure. Superheat, subcooling and amp draw separate them — which is why they are measured before any compressor is condemned.
How do you charge an R-410A package unit correctly?
A package unit with a TXV is charged to subcooling, typically in the 8–12°F range, with superheat around 10–15°F as the cross-check — never by the old add-until-it-looks-right method. On a system showing high suction and soft head, charging is the expensive wrong move: if the valve is overfeeding, more refrigerant floods the compressor further and can take it out.
Can a stuck economizer make an RTU run but not cool?
Yes, and it is the first free check on a no-cool call. A damper stuck open on a 95°F day feeds the unit hot outside air, the space climbs, and the gauges can look like a refrigerant fault because the load is artificial. Verify damper position against the minimum-position setting and feel whether the mixed air is hot before touching a gauge to the unit.
RUN THIS CASE YOURSELF
Paste your own readings into the TradesBrain demo — this case is already loaded in the demo box there; hit RUN DIAGNOSTIC and the reasoning streams back in about a minute. To run your own call, clear the box and type your pressures, temperatures and what you have already checked. It handles HVAC, diesel, small engine and industrial equipment the same way; see the diesel version of this walkthrough in 6.7 Power Stroke cranks but won't start. The demo is free; the full Technician pass is $19, sold through the same page. Both worked cases are collected in the worked-case index.